 Z-VAT-DC-4000-HS 


Bipolar DC voltage detector, 1500-4000 V. Emb. C. Probe tip Ø8 mm. Clamp.

Application:

System for checking the absence of voltage on a network supplied with direct current from 1,500 V to 4,000 V:

  • Presence of voltage indicated by the lighting up of 6 red LEDs and the emission of an audible signal.
  • Function control of the integrated device which validates all detector functions. :
    1. Contact the handle's magnetic shoe with the rail and shunt the assembly by making contact between the magnetic handle and the contact hook;
    2. Press the test button: 6 red LEDs light up, audible signal sounds;
    3. Release the test button: momentary illumination of the 6 green LEDs.

Features:

This system consists of :

  • Acoustic and luminous 1 500-4 000 V DC voltage detector with C fitting;
  • 8 mm diameter contact tip electrode;
  • Rail contact clamp;
  • 8 m connecting cable;
  • Soft case.

Data Sheet




Reference Operating Voltage DC Weight (kg)